What does this calculator do?
Server energy is power multiplied by time. This calculator turns a fleet — a server count, an average draw in watts, hours per day and a number of days — into kilowatt-hours, and separates the IT load from the facility load. The separation matters because cooling, power distribution and losses are not free: PUE, power usage effectiveness, is the ratio of total facility energy to IT energy, so a PUE of 1.5 means the room consumes half again as much as the servers alone. If you enter a price per kWh, the tool multiplies it out; the currency and the tariff are entirely yours, and no rate is looked up anywhere. Everything is computed in your browser from the values you type. Nothing is looked up on the network — there is no ping, no DNS query, no WHOIS and no geolocation.
Formula
Watts times hours gives watt-hours; divide by 1,000 for kWh, then apply PUE.
itKwhPerDay = serverCount × wattsPerServer × hoursPerDay ÷ 1000 facilityKwhPerDay = itKwhPerDay × PUE totalKwh = facilityKwhPerDay × days cost = totalKwh × pricePerKwh
How to use it
Enter the number of servers and the average power draw per server in watts — the average under your real load, not the power-supply rating, which is a maximum and usually far above what the machine actually draws. Set hours per day (24 for always-on) and the number of days in the period. Add a PUE if you want facility overhead included: a modern efficient data centre is around 1.1–1.3, a typical enterprise room 1.5–2.0. Leave PUE at 1 for IT load only. The price per kWh is optional and stays in whatever currency you use.
Worked example
Ten servers averaging 450 W, running 24 hours a day: 10 × 450 × 24 ÷ 1000 = 108 kWh per day of IT load. With a PUE of 1.5 the facility uses 162 kWh per day, so over 30 days the total is 4,860 kWh. Annualised that is 59,130 kWh, at an average continuous load of 6.75 kW.
Frequently asked questions
Should I use the power-supply rating for watts?
No. A 750 W supply describes its maximum output, not consumption. A typical server draws far less in normal operation. Use a measured average from the BMC, the PDU or a facility monitoring system if you can.
What exactly does PUE include?
PUE is total facility energy divided by IT equipment energy, so it captures cooling, UPS and distribution losses, and lighting. A PUE of 1.0 would mean zero overhead, which is not achievable; anything below 1.0 indicates a measurement error.
Is the cost figure a bill estimate?
It is a straight multiplication of energy by the single price you entered. Real invoices add demand charges, time-of-use tariffs, taxes, transmission fees and contract terms, so treat it as an order-of-magnitude figure only.
Sources
- ISO/IEC 30134-2 — Power Usage Effectiveness (PUE): the standard definition of the data-centre facility-to-IT energy ratio applied to the power results.
- BIPM — The International System of Units (SI Brochure): the watt and the kilowatt-hour, used for the energy and average-load figures.
- Nominal capacity model used here: vCPU capacity = physical cores × oversubscription ratio, and usable RAM = installed RAM − reserved RAM. NUMA topology, hypervisor scheduling, memory ballooning, workload bursts and licence limits are not modelled.